The Advisability of Employment of Renewable Energy Sources in DHW Systems in the Kindergarten

View/ Open
Author
Anna Krawczyk, Dorota
Rodero Serrano, Antonio
WITKOWSKA, Agata
Wądołowska, Bernadetta
Publisher
MDPIDate
2019Subject
Heat pumpsSolar collectors
Renewable energy
DHW
METS:
Mostrar el registro METSPREMIS:
Mostrar el registro PREMISMetadata
Show full item recordAbstract
This research aims to show the advisability of usage of selected renewable energy sources for domestic hot water (DHW) installations in buildings located in Poland and Spain. The analysis was conducted for a typical kindergarten, an example of buildings with high density of people and stable profile of usage, as opposed to schools which are closed during summer holidays. We took into account national regulations to estimate heat demand. Then applying solar collectors and heat pumps to use as a monovalent energy sources were considered. The total cost of the system with solar collectors in Poland was found to be 1.4 times higher than in Spain, whereas the difference in a case of air heat pumps was 18%. Moreover efficiency of solar collector and heat pump systems were found as 49.56% for Warsaw, 52.29% for Madrid with coefficient of performance (COP) 2.2 and 2.55 respectively, therefore simple payback time (SPBT) of investment was estimated in a range between 6–12 years for solar collectors and 5–6 years for heat pumps.